VDS-Based Timing Measurement for Medium-Voltage GIS Circuit Breakers

Testing circuit breakers with inaccessible main contacts presents a significant challenge, particularly in metal-clad switchgear and fixed-mounted medium-voltage gas-insulated switchgear (GIS). Conventional timing measurements require direct access to the main contacts, which is often not possible with these types of installations.

To address this challenge, DV Power has implemented VDS-based timing measurement functionality in its CAT100, CAT250, and CAT500/505 Circuit Breaker Analyzers, providing a practical solution for testing circuit breakers without direct access to their main contacts.

How Does VDS-Based Timing Measurement Work?

The Voltage Detection System (VDS) is an integrated system used to detect the presence or absence of voltage in medium-voltage switchgear. It typically uses a capacitive voltage divider to provide a low-voltage signal corresponding to the voltage in the main circuit.

The VDS-based timing measurement method uses these existing voltage signals to determine circuit breaker opening and closing times.

Instead of connecting measurement cables directly to the main contacts, the analyzer is connected to the VDS measuring points on the switchgear panel. By monitoring changes in voltage signals for each phase, the instrument determines the breaker operation times.

The measurement can be performed while the switchgear remains energized, eliminating the need to isolate the equipment solely to access the main contacts, provided the switchgear configuration and approved safety procedures permit the test.

VDS Signal Waveforms Used for Timing Detection

Testing Capabilities with DV Power CAT Analyzers

The VDS method has been implemented in the CAT100, CAT250, and CAT500/505 Series, using their analog measurement channels to record voltage signals from the VDS interface.

First-Trip Testing

One of the key benefits of VDS-based timing measurement is the possibility of performing a First-Trip test.

A First-Trip test records the first opening operation of a circuit breaker that has remained closed for an extended period, sometimes several years.

This measurement is particularly valuable because mechanical issues caused by prolonged inactivity, such as lubricant aging or increased mechanical friction, may affect the first operation but become less apparent after subsequent switching operations.

By recording the first opening operation, maintenance personnel can assess the circuit breaker’s behavior under actual operating conditions and identify potential problems before they develop into more serious failures.

A Practical Approach to GIS Circuit Breaker Testing

With VDS functionality implemented in the CAT100, CAT250, and CAT500/505 Series, DV Power continues to expand the testing capabilities of its circuit breaker analyzers, supporting more comprehensive condition assessment and maintenance of medium-voltage switchgear.

For more information about VDS-based timing measurement and its compatibility with your switchgear, explore our CAT100, CAT250, and CAT500 Series, and contact us to request a quote.