Tap Changer & Winding Analyzers TWA40D

quote



Overview


The Tap Changer & Winding Analyzer TWA40D is designed for six-winding resistance measurement and simultaneous three-phase on-load tap changer analysis of both the primary and the secondary transformer windings. This is performed with a one single-step cable setup, with test currents of up to 40 A. Each transformer configuration has a special measurement algorithm which is optimized for the fast stabilization of test results.

Additional testing mode, Quick YN, is enabled by the DV-Win software. In this mode, it is possible to measure the resistances of three transformer windings in the YN configuration simultaneously. It is also possible to test the resistances of all tap changer positions of all three phases in a single pass through the tap changer positions.

Accessories

Included accessories

  • DV-Win PC software
  • Ground PE cable
  • USB cable
  • Built-in Tap Changer Control Unit
  • Tap Changer Control cable set 5 m (16.4 ft)
  • USB flash drive feature
  • Mains power cable
Recommended accessories

  • H winding test cable set, 4 x 10 m (38.8 ft) with TTA clamps
  • X winding test cable set, 4 x 10 m (38.8 ft) with TTA clamps
  • Current clamp 30 / 300 A power supplied from the instrument with 5 m (16.4 ft) extension
  • Cable plastic case
  • Transport case
Optional accessories

  • Test shunt 1 mΩ (150 A / 150 mV)
  • H winding test cable set, 4 x 15 m (49.2 ft) with TTA clamps
  • X winding test cable set, 4 x 15 m (49.2 ft)with TTA clamps
  • H winding test cable set, 4 x 20 m (65.6 ft) with TTA clamps
  • X winding test cable set, 4 x 20 m (65.6 ft) with TTA clamps
  • Bluetooth communication module

 

Technical data

Mains Power Supply
  • Connection
according to IEC/EN60320-1; UL498, CSA 22.2
  • Mains supply
90 V – 264 V AC
  • Frequency
50/60 Hz
  • Mains supply voltage fluctuations
up to ±10 % of the nominal voltage
  • Input power
2250 VA
  • Fuse
15 A / 250 V, type F, not user replaceable
Winding Resistance Measurement
  • Test current
5 mA – 40 A DC
  • Output voltage
up to 55 V DC
  • Measurement range
0,1 μΩ – 10 kΩ
  • Typical accuracy
± (0,1 % rdg + 0,1 % F.S.)
Resolution
  • 0,1 μΩ – 999,9 μΩ
  • 1,000 mΩ – 9,999 mΩ
  • 10,00 mΩ – 99,99 mΩ
  • 100,0 mΩ – 999,9 mΩ
  • 1,000 Ω – 99,99 Ω
  • 100,0 Ω – 999,9 Ω
  • 1000 Ω – 9999 Ω
    • 0,1 μΩ
    • 1 μΩ
    • 10 μΩ
    • 0,1 mΩ
    • 10 mΩ
    • 0,1 Ω
    • 1 Ω
OLTC Dynamic Resistance Measurement
  • Sampling rate
0,1 ms
  • Automatic open circuit detection and warning
  • Transition current ripple measurement
  • Transition time measurement using DV-Win software
  • Timing measurement of different transition changes using DV-Win graph analysis tools
AC Current Measurement Channel
  • Resolution
0,1 ms
  • Amplitude resolution
16 bit
Computer Interface
  • Computer Interface
USB
Optional: RS232
Data Storage
  • Data Storage
500 internal memory positions; USB flash drive feature enables storage of a huge number of measurements
Environment conditions
  • Operating temperature
–10°C to +55°C / 14 F to 131 F
  • Storage and transportation
–40°C to +70°C / -40 F to 158 F
  • Humidity
5 % – 95 % relative humidity, non condensing
Dimensions and Weight
  • Dimensions
480 mm x 197 mm x 395 mm
18.9 in x 7.8 in x 15.6 in
  • Weight
12,8 kg / 28.3 lbs
Warranty
  • Warranty
three years
Safety

  • Low Voltage Directive 2014/35/EU (CE Conform)

  • Applicable standards, for a class I instrument, pollution degree 2,
       Installation category II : IEC EN 61010-1

  • CAN/CSA-C22.2 No. 61010-1

Electromagnetic Compatibility (EMC)

  • Directive 2014/30/EU (CE Conform)

  • Applicable standard EN 61326-1

All specifications listed herein are valid at the ambient temperature of + 25 °C (77°F) and with the recommended accessories included.

Specifications are subject to change without notice.

DV-Win

The DV-Win software enables control and observation of the test process, as well as saving and analyzing the results on a PC. It pro-vides a test report, arranged in a selectable form as an Excel spreadsheet, PDF, Word, or ASCII format. The software provides an OLTC (tap changer) condition assessment through analysis of the graphs representing dynamic resistance values during the tap changer transitions. Additionally, the DV-Win measures and calculates the OLTC transition time, the ripple and the winding resistance for each tap changing operation. The standard interface is USB. RS232 is optional. Additional testing mode, Quick YN, is enabled by the DV-Win software. In this mode, it is possible to measure the resistances of three transformer windings in the YN configuration simultaneously. It is also possible to test the resistances of all tap changer positions of all three phases in a single pass through the tap changer positions.

Download


Download brochure


Version: 402
Published: 2016-08-05