Turns Ratio Tester TRT63C

quote


Overview


TRT63C is a three-phase, fully automatic test set specially designed for turns ratio, phase shift and excitation current measurements of power, distribution and instrument transformers. TRT63C determines transformer turns ratio by accurately measuring the voltages across the unloaded transformer windings and then displaying a ratio of these voltages.

  • Test voltages from 1 V AC up to 250 V AC
  • Ratio range 0,8 – 50 000
  • The best ratio accuracy of 0,03%
  • Built-in tap changer control unit
  • Built-in USB flash drive
  • True three-phase and single-phase test
  • Automatic vector group detection
  • Detailed analysis of test results using DV-Win software
  • Pre-programming test-plans deploying DV-Win software
  • Lightweight – only 9 kg

 

TRT63C is the most accurate turns ratio tester on the market. True three-phase test voltage allows testing any type of transformer, including special transformers like phase shifting, arc furnace, rectifier transformers, etc.

Accessories

Included accessories

  • DV-Win PC software
  • Ground (PE) cable
  • USB cable
  • Built-in Tap Changer Control Unit
  • Tap Changer Control cable set
       5 m (16.4 ft)
Recommended accessories

  • H winding test lead set, 4 x 10 m    (32.8 ft) with TTA clamps    (compatible with TWA and TRT    series)
  • X winding test lead set, 4 x 10 m    (32.8 ft) with TTA clamps    (compatible with TWA and TRT    series)
  • Cable plastic case – large size
  • Transport case
Optional accessories

  • Cable plastic case – small size
  • Cable plastic case – medium size
  • Cable plastic case with wheels –    medium size
  • Cable plastic case with wheels –    large size
  • Plastic transport case
  • Plastic transport case with    wheels
  • Built-in thermal printer 112 mm    (4.4 in)
  • Thermal paper roll 112 mm
       (4.4 in)
  • Bluetooth communication module
  • Inverter 12 V DC to 230 V AC,
       50 Hz
  • Cable bag
  • H winding test lead set, 4 x 5 m    (16.4 ft) with TTA clamps    (compatible with TWA and TRT    series)
  • X winding test lead set, 4 x 5 m    (16.4 ft) with TTA clamps    (compatible with TWA and TRT    series)
  • H winding test lead set, 4 x 15 m    (49.2 ft) with TTA clamps    (compatible with TWA and TRT    series)
  • X winding test lead set, 4 x 15 m    (49.2 ft) with TTA clamps    (compatible with TWA and TRT    series)
  • H winding test lead set, 4 x 20 m    (65.6 ft) with TTA clamps    (compatible with TWA and TRT    series)
  • X winding test lead set, 4 x 20 m    (65.6 ft) with TTA clamps    (compatible with TWA and TRT    series)
  • H winding cable extension set,
       4 x 5 m (16.4 ft) (compatible with
       TWA and TRT series)
  • X winding cable extension set,
       4 x 5 m (16.4 ft) (compatible with
       TWA and TRT series)
  • H winding cable extension set,
       4 x 10 m (32.8 ft) (compatible with
       TWA and TRT series)
  • X winding cable extension set,
       4 x 10 m (32.8 ft) (compatible with
       TWA and TRT series)
  • H winding cable extension set,
       4 x 15 m (49.2 ft) (compatible with
       TWA and TRT series)
  • X winding cable extension set,
       4 x 15 m (49.2 ft) (compatible with
       TWA and TRT series)
  • H winding test lead set, 4 x 5 m    (16.4 ft) with TTA clamps    (compatible with TRT series only)
  • X winding test lead set, 4 x 5 m    (16.4 ft) with TTA clamps    (compatible with TRT series only)
  • H winding test lead set, 4 x 10 m    (32.8 ft) with TTA clamps    (compatible with TRT series only)
  • X winding test lead set, 4 x 10 m    (32.8 ft) with TTA clamps    (compatible with TRT series only)
  • H winding test lead set, 4 x 15 m    (49.2 ft) with TTA clamps    (compatible with TRT series only)
  • X winding test lead set, 4 x 15 m    (49.2 ft) with TTA clamps    (compatible with TRT series only)
  • H winding test lead set, 4 x 20 m    (65.6 ft) with TTA clamps    (compatible with TRT series only)
  • X winding test lead set, 4 x 20 m    (65.6 ft) with TTA clamps    (compatible with TRT series only)
  • H winding cable extension set,
       4 x 5 m (16.4 ft) (compatible with
       TRT series only)
  • X winding cable extension set,
       4 x 5 m (16.4 ft) (compatible with
       TRT series only)
  • H winding cable extension set,
       4 x 10 m (32.8 ft) (compatible with
       TRT series only)
  • X winding cable extension set,
       4 x 10 m (32.8 ft) (compatible with
       TRT series only)
  • H winding cable extension set,
       4 x 15 m (49.2 ft) (compatible with
       TRT series only)
  • X winding cable extension set,
       4 x 15 m (49.2 ft) (compatible with
       TRT series only)
  • TRTC Verification Calibrator with    associated cables
  • TWA-TRT safety switchbox with    associated cables

 

Technical Data


Mains Power Supply
  • Connection
according to IEC/EN60320-1; UL498, CSA 22.2
  • Mains supply
90 – 264 V AC, or 110 – 350 V DC
  • Frequency
50/60 Hz
  • Input power
250 VA
  • Fuse
2 A / 250 V, type F, but not user replaceable
Output data
  • Test voltage
1 V, 8 V, 40 V, 80 V, 250 V AC
3 x (1, 8, 40, 80, 250)√3 V AC
Measurement
  • Ratio measuring range
0,8 – 50 000 (5-digit resolution)
  • Excitation current range
0 – 2 A
  • Typical excitation current accuracy
± (0,25% + 500 μA)
  • Excitation current resolution
    • 0,0000 – 9,9999 mA
    • 10,000 – 99,999 mA
    • 100,00 – 999,99 mA
    • 1,0000 – 2,0000 A
  •  
    • 0,1 μA
    • 1 μA
    • 10 μA
    • 100 μA
  • Phase angle range
360º
  • Typical phase angle accuracy
±0,05º
  • Phase angle resolution
0,01º
Display
  • Display
LCD screen 20 characters by 4 lines; LCD display with backlight, visible in bright sunlight
Interface
  • Interface
TRT63C is equipped with an USB port to connect to an external computer
Test Result Storage
  • Test Result Storage
TRT63C can store 200 transformer test records; Each test record can store 50 test readings
Environment conditions
  • Operating temperature
–10°C – +55°C / 14 F – 131 F
  • Storage and transportation
–40°C – +70°C / -40 F – 158 F
  • Humidity
5 % – 95 % relative humidity, non condensing
Dimensions and Weight
  • Dimensions
480 mm x 190 mm x 385 mm
18.90 in x 7.48 in x 15.16 in
  • Weight
9 kg / 19.8 lbs
Safety

  • Low Voltage Directive 2014/35/EU (CE Conform)

  • Applicable standards, for a class I instrument, pollution degree 2,
       Installation category II : IEC EN 61010-1

  • CAN/CSA-C22.2 No. 61010-1

Electromagnetic Compatibility

  • Directive 2014/30/EU (CE Conform)

  • Applicable standard EN 61326-1

All specifications listed herein are valid at the ambient temperature of + 25 °C (77°F) and with the recommended accessories included.

Specifications are subject to change without notice.

DV Win


trt_dvwin

The software provides numerous advantages, such as downloading test results from the instrument, acquisition of test results, creating graphs for easier analysis, creating test reports and saving them in several different formats.

When creating test plan, the DV-Win enables automatic calculation of nameplate voltages for all tap positions. The user is allowed to edit these voltages, save the test plan and recall it onsite. All results are displayed both numerically and graphically, making analysis as easy as possible. Test report, generated with single click, can be quickly customized, and directly printed or saved.

Download


Download brochure


Version: 317
Published: 2017-03-29

Back To Top