Tap Changer Analyzer & Winding Ohmmeter RMO25TD

quote



Overview


The Tap Changer Analyzer & Winding Ohmmeter RMO25TD instrument is designed for winding resistance measurement of inductive objects, and for a tap changer analysis. The RMO25TD instrument is based on the state of the art technology, using the most advanced switch mode technology available today. The RMO25TD instrument is accurate (0,1%), powerful (up to 25 A) and lightweight (9,5 kg / 20.9 lbs). It generates a true DC ripple free current with automatically regulated measurement and discharging circuit.

The RMO25TD instrument can perform a simple, quick and reliable transformer on-load tap changer condition assessment. This instrument enables measurements of a winding resistance in every tap position, current ripple values (percentage of a current drop during a tap change) and transition times during the tap changes. Problems with a connection, contacts, and selector/diverter switch operation (tap change with interruption) can be detected with these measurements.

Accessories

Included accessories

  • DV-Win PC software including USB cable
  • Built-in Tap Changer Control Unit
  • Tap Changer Control cable 5 m (16.4 ft)
  • Mains Power cable
  • Ground (PE) cable
Recommended accessories

  • Current cables 2 x 10 m 10 mm2 (32.8 ft, 7 AWG) and Sense cables
    2 x 10 m (32.8 ft) with TTA clamps
  • Sense cables 2 x 10 m (32.8 ft) with TTA clamps
  • Current connection cable 1 x 5 m 10 mm2 (16.4 ft, 7 AWG) with TTA clamps
  • Cable bag
  • Current clamp 30/300 A supplied from the instrument with extension
    5 m (16.4 ft)
Optional accessories

  • Test shunt 150 A / 150 mV
  • Thermal printer 80 mm (3.15 in) (built-in)
  • Transport case
  • Current cables 2 x 15 m 10 mm2 (49.2 ft, 7 AWG) and Sense cables
    2 x 15 m (49.2 ft) with TTA clamps
  • Current cables 2 x 20 m 16 mm2 (65.6 ft, 5 AWG) and Sense cables
    2 x 20 m (65.6 ft) with TTA clamps
  • Bluetooth communication module
  • PT100 temperature indicator

Technical data

Winding Resistance Measurement

  • Test currents: 5 mA – 25 A DC
  • Output voltage: up to 55 V DC
  • Measurement range: 0,1 μΩ – 10 kΩ
  • Typical accuracy:
    ± (0,1% rdg + 0,1% F.S.) for 0,1 μΩ – 1,999 kΩ range
    ± (0,2% rdg + 0,1% F.S.) for 2 kΩ – 9,999 kΩ range

 

Data Storage

  • 1000 internal memory positions
  • USB flash drive feature enables storage of a huge number of measurements
AC Current Measurement Channel

  • Resolution: 0,1 ms
  • Amplitude resolution: 16 bit
Current Clamp Meter Specifications

  • Current range: 30 / 300 A
  • Nominal current: 300 ARMS or 450 A DCPK
  • Frequency range: DC to 20 kHz (-3 dB)
Printer (optional)

  • Thermal printer
  • Paper width 80 mm

 

Mains Power Supply

  • Connection according to IEC/EN60320-1;
    UL498, CSA 22.2
  • Mains supply: 90 V – 264 V AC
  • Frequency: 50/60 Hz
  • Mains supply voltage fluctuations up to ±10 % of the nominal voltage
  • Input power: 1800 VA
  • Fuse 15 A / 250 V, type F, not user replaceable
Environmental conditions

  • Operating temperature: -10 ºC – + 55 ºC / 14 F – +131 F
  • Storage & transportation: -40 ºC – + 70ºC / -40 F – +158 F
  • Humidity 5 % – 95 % relative humidity, non condensing

Resolution

  • 0,1 μΩ – 999,9 μΩ: 0,1 μΩ
  • 1,000 mΩ – 9,999 mΩ: 1 μΩ
  • 10,00 mΩ – 99,99 mΩ: 10 μΩ
  • 100,0 mΩ – 999,9 mΩ: 0,1 mΩ
  • 1,000 Ω – 9,999 Ω: 1 mΩ
  • 10,00 Ω – 99,99 Ω: 10 mΩ
  • 100,0 Ω – 999,9 Ω: 0,1 Ω
  • 1,000 kΩ – 9,999 kΩ: 1 Ω

 

OLTC Dynamic Resistance Measurement

  • Sampling rate: 0,1 ms
  • Automatic open circuit detection and warning
  • Transition current ripple measurement
  • Transition time measurement using DV-Win software
  • Timing measurement of different transition changes using DV-Win graph analysis tools
Computer Interface

  • USB
  • Optional: RS232

 

Warranty

  • Three years
Dimensions and Weight

  • Dimensions: 405 mm x 170 mm x 335 mm
    16 in x 6.7 in x 13.2 in
  • Weight: 10,0 kg / 22,0 lbs

 

Safety

  • Low Voltage Directive 2014/35/EU (CE Conform)
  • Applicable standards, for a class I instrument,    pollution degree 2,
       Installation category II : IEC EN 61010-1
  • CAN/CSA-C22.2 No. 61010-1
Electromagnetic Compatibility

  • Directive 2014/30/EU (CE Conform)
  • Applicable standard EN 61326-1

All specifications listed herein are valid at the ambient temperature of + 25 °C (77°F) and with the recommended accessories included.

Specifications are subject to change without notice.

DV-Win

The DV-Win software enables control and observation of the test process, as well as saving and analyzing the results on a PC. It provides a test report, arranged in a selectable form as an Excel spreadsheet, PDF, Word, or ASCII format. The software provides an OLTC (tap changer) condition assessment through analysis of the graphs representing dynamic resistance values during the tap changer transitions.

Additionally, the DV-Win measures and calculates the OLTC transition time, the ripple and the winding resistance for each tap changing operation. It also enables the recording of tap changer motor current, which is used for detecting motor and mechanical problems.
The software can also perform the calculations necessary for the “Heat Run” test.

The standard interface is USB. RS232 is optional.

Download


Download brochure


Version: 303
Published: 2016-07-12

Back To Top