Circuit Breaker Analyzer & Timer CAT124A

quote



Overview



ftp://natasa@dv-power.com@ftp.dv-power.com/wp-content/uploads/2013/09/CAT126_125_front.png

  • Timing and motion measurement
  • 12 timing channels (3×4) for main and resistive contacts
  • 6 timing channels for auxiliary inputs
  • 3 transducer input channels
  • 4 additional analog input channels
  • Detailed analysis of test results using DV-Win software

The Circuit Breaker Analyzer & Timer CAT124A instrument utilizes the latest improvements for safe and fast testing, with unique technical capabilities for additional diagnostics of circuit breakers. Sophisticated design ensures efficient and reliable operations in high-voltage substations and industrial environments.

First trip test
A “First trip” analysis is important to determine a condition of the coil operating mechanism. A circuit breaker spends most of its lifetime conducting a current without any operation. Once the protective relay detects a problem, the circuit breaker, that was idle for maybe a year or longer, has to operate as fast as possible. However, if the circuit breaker has not been operated for a long time, the latch friction may increase. Information about the latch friction can be obtained from the coil current waveform recorded during the “First trip” test.

Accessories

Included accessories

  • DV-Win software
  • USB cable
  • Mains power cable
  • Ground (PE) cable
Recommended accessories

  • Main contact cables 5 m (16.4 ft) with SCT clamps
  • Main contact cables Extension 10 m (32.8 ft)
  • Coil control cable set 5 m (16.4 ft) with banana plugs
  • Coil supply cable set 2 x 5 m 2,5 mm2 (16.4 ft, 13 AWG) with banana plugs
  • Auxiliary contacts cable set 10 x 5 m (16.4 ft) with banana plugs
  • External trigger cable 5 m (16.4 ft) with banana plugs
  • Analog channels cable set 8 x 5 m (16.4 ft) with banana plugs
  • Cable plastic case – large size
  • Transport case
Optional accessories

  • Current clamp 30/300 A power supplied from the instrument with adapter 5 m (16.4 ft)
  • Current clamp 30/300 A with internal battery supply and extension 5 m (16.4 ft)
  • Thermal printer 112 mm (4.4 inch) (built-in)
  • Thermal paper roll
  • Main contact cables Extension 5 m (16.4 ft)
  • Main contact cables Extension 15 m (49.2 ft)
  • Cable plastic case with wheels – large size
  • Digital rotary transducer with 5 m (16.4 ft) connection cable
  • Linear analog transducer 150 mm (5.9 in) with 5 m (16.4 ft) connection cable
  • Linear analog transducer 225 mm (8.85 in) with 5 m (16.4 ft) connection cable
  • Linear analog transducer 300 mm (11.8 in) with 5 m (16.4 ft) connection cable
  • Linear analog transducer 500 mm (19.68 in) with 5 m (16.4 ft) connection cable
  • Universal transducer mounting kit
  • Universal transducer mounting kit – extended version
  • Doble transducer adapter
  • Linear to rotary convertor

Technical data

Main contact inputs

  • Number of contact inputs: 12 (3 x 4), 4 per phase.
  • Each channel detects main and pre-insertion resistor contacts.
    • Closed ≤ 10 Ω,
    • Resistor contacts range 10 Ω to 5 kΩ,
    • Open ≥ 5 kΩ
    • Open circuit voltage: 20 V DC
    • Short circuit current 50 mA
  • Each channel measures resistance of pre-insertion resistors

 

Coil driver

  • Number of channels: 4 (3 Open and 1 Close coil)
  • Four separate outputs for coil triggering
  • Driver characteristics: 300 V DC max, 35 A DC max
  • Electronic drivers: it provides superior timing control
  • Overcurrent and overvoltage protection

 

Breaker operation

  • Close (C),
  • Open (O),
  • Close-Open (C-O),
  • Open-Close (O-C),
  • Open-Close-Open (O-C-O)
  • First trip test

User can select any desired test sequence

DC output

  • 24 V voltage supply for current clamps

 

Analog inputs

  • 4 channels – Coil current measurement
  • 4 Voltage channels, each channel has four measurement ranges: ±0,5 V, ±2,5 V, ±60 V and ±300 V AC/DC
  • The analog inputs are isolated with respect to all other circuits

 

Printer (optional)

  • Thermal printer
  • Graphic and numeric printout
  • Paper width 112 mm

 

Mains Power Supply

  • Connection according to IEC/EN60320-1;
    UL498, CSA 22.2
  • Mains supply: 90 V – 264 V AC
  • Frequency: 50/60 Hz
  • Mains supply voltage fluctuations up to ±10 % of the nominal voltage
  • Input power: 250 VA
  • Fuse 2 A / 250 V, type F, not user replaceable

 

Environmental conditions

  • Operating temperature: -10 ºC – + 55 ºC / 14 F – +131 F
  • Storage & transportation: -40 ºC – + 70ºC / -40 F – +158 F
  • Humidity 5 % – 95 % relative humidity, non condensing

 

Auxiliary inputs

  • Number of channels: 6, galvanically isolated (external trigger input can be used as a sixth auxiliary input)
  • User selectable: dry or wet
    • Contact sensing (dry):
      • Open circuit voltage 24 V DC,
      • Short circuit current 5 mA
    • Voltage sensing (wet):
      • Working voltage 300V DC, 250V AC
      • Low activation mode ± 5V
      • High activation mode ±10V
  • Overcurrent and overvoltage protection

 

Time measurement
Time measurement resolution:

  • 0,1 ms for 2 s test duration;
  • 1 ms for 20 s test duration;
  • 10 ms for 200 s test duration;

Time accuracy 0,05% of the reading ± resolution

Current measurement

  • Current measurement for Open and Close coil, 4 channels, Hall-Effect sensor
  • Range ±35A DC to 5 kHz
  • Accuracy ± (0,5 % rdg + 0,1 % FS)
  • Graphic presentation: currents waveform is displayed with resolution of 0,1 ms

 

Time measurement triggers

  • External trigger: 2 channels, input voltage: 10 V – 300 V AC/DC
  • Coil currents: threshold level user selectable
  • Auxiliary inputs
  • Analog inputs: threshold level user selectable, positive or negative

 

Universal transducer inputs

  • 3 digital travel transducer channels
  • Digital rotary transducers: 2500ppr
  • 3 analog travel transducer channels
  • Analog transducer input measurement resolution: 16 bit.
  • Internal supply for linear transducer: 5 V DC

 

Warranty

  • Three years

 

Dimensions and Weight

  • Dimensions: 480 mm x 197 mm x 395 mm
    18.9 in x 7.8 in x 15.6 in
  • Weight: 10,5 kg / 23.1 lbs

 

Safety

  • Low Voltage Directive 2014/35/EU (CE Conform)
  • Applicable standards, for a class I instrument,
       pollution degree 2,
       Installation category II : IEC EN 61010-1
  • CAN/CSA-C22.2 No. 61010-1
Electromagnetic Compatibility

  • Directive 2014/30/EU (CE Conform)
  • Applicable standard EN 61326-1

All specifications listed herein are valid at the ambient temperature of + 25 °C (77°F) and with the recommended accessories included.

Specifications are subject to change without notice.

DV-Win

Viewing and overlaying several graphs for complete and easy test result comparison. Selecting the measurement points and intervals using two available cursors. Zoom and pan graph feature. Specific test sequence setup. Customized configuration of test result graphs.

For the CAT form of DV-Win software there is Help menu available, with detailed instructions and explanations of all functions and features.

Download


Download brochure