Battery Load Unit BLU220TK

quote


Overview

BLU220KTBLU220KT

The Battery Load Unit – BLU220TK is the stand-alone or a PC-controlled battery capacity test set, based on the state-of-the-art technology. Its design is using the most advanced power electronics solutions with coolers and fans integrated into device itself.

The BLU220TK device is lightweight (15,1 kg / 33 lb.) and developed to meet a customer’s wide ranging test procedure requirements (standardized as well as customized). Using the BLU220TK device, the capacity test is performed in an accurate, user-friendly way in accordance with the battery testing standards (IEEE 450-2010 / 1188-2005 / 1106-2015, IEC 60896-11/22 and other relevant standards).
Discharging can be performed at constant current, constant power, constant resistance or in accordance with a pre-selected load profile. The discharge test can be conducted even in case a battery remains connected to the load – by measuring the load current during the process.

The BLU220TK device provides the discharge current of up to 330 A and may be applied to battery strings with up to    60 V voltage level.


Main Features

  • Lightweight – 15,1 kg (33 lb.)
  • Powerful – discharge power up to 18,6 kW
  • Voltage measurement range: up to 75 V DC
  • Discharge current – up to 330 A DC
  • Expandable for larger banks using BXL-T extra load units
  • Current measurement range using Current Probe 0 – 300 / 1 000 A DC
  • User – adjustable alarm and shutdown parameters to prevent excessive discharge
  • Testing without disconnecting the regular load
  • Detailed test analysis using DV-B Win software
  • Test resume feature in case of interrupted power supply


Accessories

Included accessories

  • Mains power cable
  • Ground (PE) cable
  • USB cable
  • DV-B Win software
  • Transport case
Recommended accessories

  • Current cables 2 x 3 m 50 mm2 (9.84 ft, 2 AWG) with alligator clamps (A4) isolated
  • Cable bag
Optional accessories

  • Current cables 2 x 5 m 70 mm2 with alligator clamps (A4) isolated
  • Current cables 2 x 10 m 70 mm2 with alligator clamps (A4) isolated
  • Extension cables 2 x 5 m 70 mm2
  • Current clamp 30/300 A power supplied from the instrument with extension 5 m

Technical data

Mains Power Supply

  • Connection: according to IEC/EN60320-1; C320
  • Voltage: 90 V – 264 V AC, 50 / 60 Hz, single-phase
  • Input power: 150 VA
  • Fuse: 2 A / 250 V, type F

Dimensions and Weight

  • Dimensions (D x W x H) without handle: 560 mm x 221 mm x 355 mm
    22 in x 8.7 in x 14 in
  • Weight: 15,1 kg / 33 lb.

Maximum discharge current & power

Battery voltage 6 V 12 V 24 V 48 V 60 V
Min-Max voltage (V) 5,25 7,05 10,5 14,1 21,0 28,2 42,0 56,4 52,5 70,5
Maximum current (A) 100 200 330 330 250
  • Power: 18,6 kW

Measurement

Internal voltage measurement

  • Range: 0 – 75 V DC
  • Resolution: 0,1 V
  • Typical accuracy: ± 0,5% of reading ± 0,1 V

Internal current measurement

  • Range: 0 – 400 A DC
  • Resolution: 0,1 A
  • Typical accuracy: ± 0,5% of reading ± 0,2 A

Current measurement with current probe

  • Range: 0 – 300 / 1000 A DC
  • Resolution: 0,1 A DC

Time measurement

  • Typical accuracy: ± 0,1 % of reading ± 1 sec

Display

  • LCD screen 20 characters by 4 lines with backlight, visible at bright sunlight

Display range

  • Current: 0 – 2 999,9 A DC
  • Voltage: 0 – 999,9 V DC
  • Time: 00h:00m:00s – 99h:59m:59s

Capacity range and resolution

  • Range: 0 – 9999,9999 Ah
  • Resolution: 0,0001 Ah

Warranty

  • The transport case is considered as the standard accessory for this device. Ordering the device with it provides the 3-year manufacturer’s warranty. Avoiding to include it in a purchase order will provide 15 calendar month warranty.

Environmental conditions

  • Operating temperature: -10 °C to +50 °C / 14 °F to +122 °F
  • Storage & Transportation temperature: -40 °C to +70 °C / -40 °F to +158 °F
  • Humidity: 90%, non-condensing
  • Pollution degree 2

Safety

  • Low Voltage Directive 2014/35/EU (CE Conform)
  • Applicable standards, for a class I instrument, pollution degree 2,
    Installation category II : IEC EN 61010-1
  • CAN/CSA-C22.2 No. 61010-1

Electromagnetic Compatibility

  • Directive 2014/30/EU (CE Conform)
  • Applicable standard EN 61326-1

All specifications listed herein are valid at the ambient temperature of + 25 °C (77°F) and with the recommended accessories included.

Specifications are subject to change without notice.

DV-B Win


The DV-B Win software is included in the price, and all its updates are free of charge. Using the DV-B Win software a test can be performed and monitored from a PC, and the results can be saved directly to a PC. Communication between the BLU-K and a PC is achieved through a USB cable. Using the DV-B Win, the results can be arranged and printed for a report in selectable formats as XLS, PDF, Word, or RTF. Also, a possibility of importing other types of data formats (jpg, png, doc) into standardized DV-B Win report is provided, as well as exporting the numerical and graphical results from the DV-B Win into a customizable report. Additionally, the software provides a possibility of setting extra parameters (cell voltage, string voltage, capacity and time) for alarming and terminating the test.


Download

Download brochure

Download brochure

Version: 306
Published: 2017-03-06

 