The value of a primary circuit contact resistance (the resistance between
two terminals of any pole of a breaker) is typically measured before a
circuit breaker is first put into service and during maintenance inspections.
Contact resistance is a value that is specified as a reference for all
kinds of circuit breakers. According to IEC 56 (now IEC62271-100) this
resistance value should be measured using a test current between 50A
and the breaker's nominal current value. According to ANSI C 37.09 the
lowest test current is 100A. Other national and international standards
specify similar regulations.
The value of the test current is usually defined by manufacturer. Most
of manufacturers (ABB, Alstom, etc.) specify test current at 200A. Some
electrical utilities have their own regulations (Vattenfall-Sweden measures
contact resistance for breakers and disconnect switches at 300A). Others
use 500A or 600A test current, while some do not exceed 100A.
Our opinion is that the current value of 300A (often even 200A) is
sufficient for correct and reliable measurement.
If there is a question about the accuracy of measurement or condition
of contacts, the measurement can be repeated using the higher current
value. Our experience shows better result using the CONT mode - continuous
current measurement at 200A to 300A in the duration of 50sec.
Higher test currents increase the accuracy, but the test current above
300A provide insignificant improvement in the accuracy. Higher currents
require bigger cables, that are heavy and make the procedure of resistance
measurement troublesome and complex, without any significant result improvements.
Conclusion:
We recommend the test current of 300A. For most situations 200A test
current is sufficient. In case of doubt, repeat the test using the Cont
mode, longer duration measurement at currents of 300A or 200A.
It is recommended to use 400A or 500A for situations where the contact
resistance measured is expected to be below 20µΩ.
Back to products
Back to support |