Print this page  |
The inductance value of a transformer depends on the current injected
in the windings. When the transformer is saturated the inductance
is minimized. A transformer is normally designed to reach saturation
when the current is 1,2 times the peak value of the no-load current.
The no-load current is normally in the range of 0,2 to 5 percent
of the nominal winding current.
When measuring the DC resistance the test current should be at least
1,2 times the no-load current of the transformer. This is to ensure
that the transformer core is saturated. Note also that the test
current is NOT to exceed approx 10-15 percent of the nominal winding
current.
Four-wire (Kelvin) measurement method is used because it provides
the best possible measurement. This ensures that the resistance
of the connecting current cables is not included in the measurement.
The test current is passed through the windings using high current
cables. The voltage drop across the windings is measured using sensing
cables. The placing of cables is very important: the current cables
should always be outside the sensing cables (see drawing). The resistance
is calculated using Ohm's law: voltage drop divided by the test
current (U=R*I i.e. R=U/I).
Always use the test instrument to discharge the energy in the windings after the measurement and before the test current is switched off.

Procedure steps:
1. Make certain that the transformer is disconnected properly and
that local safety regulations are followed.
2. Ground the test instrument.
3. Make sure that the test instrument is switched off.
4. Connect current and sensing cables according to the drawing.
5. If using a test instrument with temp sensors, connect temp sensors
properly.
6. Switch the test instrument on.
7. Set the test current to a minimum of 1,2 times the no-load current. Also
make sure that the test current does NOT exceed approx 10-15 percent of
the nominal winding current.
8. Perform the measurement.
Back to products
Back to support |
|
|