Print this page  |
| |
| Q: What is the difference between Power Boxes POB30D, POB30AD and Coil Tester & Breaker Supply units POB30D and POB30AD? |
| A: Acctualy, there is no any difference. Since POB30D, POB30DL, POB30AD and POB30ADL are not only power supply units, but also minimum trip voltage testers, their name is changed from Power Boxes to Coil Tester & Breaker Supply units. |
| Q: The POB30AD current pulse width (DC) is 140ms. However, some Chinese
customers want the pulse width of 700ms. Is it possible? Some old circuit
breakers close pulse is about 700ms. Can the pulse width be adjusted? |
A:
DC pulse width (140ms) was chosen because our German customers specified
it.
The reason is possibility because a coil could be blown in the MT Volt menu.
In the MT Volt menu by pushing TRIG button, a pre-selected DC voltage
lasting 140ms is brought to a desired coil. If coil was not actuated,
voltage automatically increases for selected step, and after 900ms pause
voltage is generated again, lasting 140ms.
If the DC pulse width is increased from 140ms to 700ms in the MT Volt menu,
the coil could be overheated and because of that burn-out.
For that reason, we can offer two possibilities for your market:
1-We can adjust DC pulse width of 700ms in the Volt DC menu, but we have to
keep pulse width of 140ms in the MT Volt menu.
2-We can adjust DC pulse width of 700ms in both, the Volt DC menu and the MT
Volt menu, but we have to increase the pause from 900ms to 2,8s in the MT
Volt menu. |
| Q: Please confirm that the POB30AD or POB30D can be equipped with the
built-in thermal printer. |
| A: Our POB30D and POB30AD are only Power Boxes, and unfortunately they are
not timers. Because of that, it does not make sense to build in a thermal
printer.
Very soon we are going to develop Power Box with the timer, and then our
POB30D and POB30AD will be equipped with the built-in thermal printer. |
| Q: I wonder if the DC voltage of the power box POB30 can be adjusted
continuously? For example, from 65V to 66V to 67V to 69V, and any value of
voltage within the specs? For example, 35V, 40V, 134V etc. |
| A: We have developed two variations of power box, POB30D and POB30AD. The
POB30D generates only DC voltage, and POB30AD generates both, DC and AC
voltages.
At our power box POB30D you can select any voltage from 10V up to 300V with
resolution of 1V.
At our power box POB30AD you can select any voltage from 10V up to 300V DC
and from 10V up to 250V AC with resolution of 1V. |
| Q: What is the procedure to do the minimal trip voltage test? |
| A: Both devices POB30D and POB30AD have built-in function intended for
automatic test of minimal trip voltage. You can choose the triggering
voltage of the closing coil (or the breaking coil) on the switch by setting
the minimal voltage, the maximum voltage and the step voltage. The device
will automatically examine the minimal trip voltage of the coil. |
| Q: What is the difference between POB30D and POB30AD? |
| A: POB30D is upgraded and more powerful version of POB30. The POB30D can
generate DC voltage at coils outputs. Besides DC voltage, the unit POB30AD
can generate AC voltage, at coils outputs. |
Q: We have bought a power supply type POB30 last year and would like to know
if this device is suitable for testing of switchgear or it is suitable only
for circuit breaker test?
Because when we supply one cell of MV switchgear (contains Siemens
protection relay, control relay, signal lamp in LV chamber) with setting
voltage of 30V, the voltage changes from 10V to 40V and is not stable. It
happens especially when the voltage is applied to binary input of relay for
testing of supervision function. |
| A: All our devices have protection schemes. If the load draws current in
excess of 26A, the voltage on our devices will start to decrease. |
| |