- Test voltages 8 V, 40 V, 100 V AC
- Ratio range 0,8 - 15 000
- Measurement of turns ratio
- Measurement of phase shift
- Measurement of excitation current
- True three-phase and single-phase test
|
Three phase Turns Ratio Tester |
TRT30 is a true three-phase, fully automatic, test set specially designed for turns ratio, phase shift and excitation current measurement of power, distribution and instrument transformers. TRT30 determines the transformer turns ratio by accurately measuring the voltages across the unloaded transformer windings and then displaying the ratio of these voltages (ratios range from 0,8 to 15 000). |
| Description |
TRT30 is based on state of the art technology, using the most advanced technique available today. The test set can be used to test single-phase and three-phase transformers, both with and without taps in accordance with the requirements of the IEC 60076-1 standard.
For three-phase measurement, the test set is connected to all three phases of the transformer to be tested. If specific vector diagrams for different types of transformers are selected, the TRT30 will run a specific test for each transformer type (i.e., single phase, Delta to y, Y to delta, Delta to delta, or Y to y) without the need to switch test hookup cables. Turns ratio, phase shift and excitation current are displayed on the display obtained with true three-phase and single-phase tests.
TRT30 lets users enter a transformer’s nameplate voltages for the turns-ratio calculation. This feature eliminates any error otherwise caused by an operator’s manual calculation. The TRT30 also compares the test result with the calculated ratio and prints out the % of error for each test. It is easy to read display and easy to follow menu. View the result on the display. There is enough memory in TRT30 to store 100 test records and each record consists of 100 test readings. All measurements are time and date stamped. The measurements can be printed on a built-in thermal printer using the Print button.
Transformer excitation current as well as phase shift angles helps to detect transformers shorted turns or unequal number of turns connected in parallel. Operating conditions messages or error messages identify incorrect test conditions, abnormal operating condition or winding problems.
TRT30 has very high ability to cancel electrostatic and electromagnetic interference in HV electric fields. It is achieved by very efficient filtration. The filtration is made utilizing appropriate hardware and software.
|
| DV-Win software |
All measurements can also be exported to a PC with the DV-Win software. The software connects a PC to TRT30 with USB cable. Using the DV-Win it is possible to report and analyze results. Also TRT30 can be controlled and test status could be viewed using the DV-Win software.
|
| Typical application |
TRT30 is programmed to automatically test turns ratio, phase shift and excitation current of power, distribution and instrument transformer types defined by CEI/IEC standards. |
| Standard accessories |
- H winding test cable 5 m, three-phase connection, clip-end terminated
- H winding test cable extension, 5 m, shielded
- X winding test cable, 5 m, three-phase connection, clip-end terminated
- X winding test cable extension, 5 m, shielded
- DV-Win PC software including USB cable
- Built-in Tap Changer Control Unit
- Tap Changer Control cable set 5 m
- Mains power cable
- Ground (PE) cable
- Cable bag
- TRTC verification calibrator
|
| Optional accessories |
- H winding test cable extension, 10 m, shielded
- X winding test cable extension, 10 m, shielded
- H winding test lead, 3 m, three-phase connection, clip-end terminated
- X winding test lead, 3 m, three-phase connection, clip-end terminated
- Built-in thermal printer
|
| |
 |
|
 |
| TRT30 |
|
Cable bag |
|
| |
| Connecting a Test Object to TRT30 |
| With TRT30 turned off, connect TRT30 to the test object. Pay attention not to replace primary and secondary cables on transformer side. |
 |
|
| |
|
| Technical data |
| 1 Mains Power Supply |
|
| - Voltage |
110 - 230 V AC |
| - Mains supply |
50 - 60 Hz |
| - Input power |
200 VA |
| - Fuse |
2 A / 250 V, type F |
| 2 Output data |
|
| - Test voltage |
8 V AC, 40 V AC, 100 V AC
3x(8, 40, 100)√3 V AC |
| - Typical Ratio Accuracy |
|
| 0,8 – 999: ±0,1 %, 1000 – 1999: ±0,2 %, 2000 – 7999: ±0,4 %, 8000 – 15000: ±0,6 %, @ 100 V AC |
| 0,8 – 999: ±0,1 %, 1000 – 1999: ±0,2 %, 2000 – 7999: ±0,4 %, 8000 – 15000: ±0,6 %, @ 40 V AC |
| 0,8 – 999: ±0,1 %, 1000 – 1999: ±0,2 %, 2000 – 7999: ±0,4 %, 8000 – 15000: ±0,6 %, @ 8 V AC |
| - Excitation current Range |
0 – 2 A |
| - Typical Excitation current Accuracy |
± 1 mA |
| - Excitation current Resolution |
0,1 mA |
| - Phase Angle Range |
360 Degrees |
| - Typical Phase Angle Accuracy |
± 0,05 Degrees |
| - Phase Angle Resolution |
0,01 Degree |
| 3 Display |
- LCD Screen: 20 Characters by 4 Lines; LCD display with backlight, viewable in bright sunlight. |
| 4 Interface |
| - TRT30 is equipped with an USB port to connect to an external computer. |
| 5 Test Result Storage |
| - TRT30 can store 100 transformer test records; each test record can store 100 test readings. |
6 Environment conditions |
| - Operating temperature -10 °C - +55 °C / 14 F - 131 F |
| - Storage temperature -40°C - +70 °C / 40 F - 158 F |
| - Maximum relative humidity 95 % non-condensing |
| - Mains supply voltage fluctuations up to ±10 % of the nominal voltage |
| - Installation/overvoltage category II |
| - Pollution degree 2 |
| 7 Dimensions and Weight |
| - Dimensions |
450 x 175 x 320 mm (W x H x D)
17,72 x 6,89 x 12,6 in
|
| - Weight |
8 kg/17,5 lbs |
| 6 Safety Standards |
| - European standards |
LVD 2006/95/EC
EN 61010-1 |
| - International standards |
IEC 61010-1
UL 61010-1
CAN/CSA-C22.2 No. 61010-1, 2nd edition, including Amendment 1 |
| 7 Electromagnetic Compatibility (EMC) |
| - CE conformity |
EMC directive 2004/108/EC |
| - Emission |
EN 61326-1 |
| - Immunity |
EN 61326-1 |
All specifications herein are valid at ambient temperature of + 25 °C and standard accessories. Specifications are subject to change without notice. |
|
| |