Winding Ohmmeter &
Tap Changer Analyzer
RMO60T

RMO60T

Brochure RMO60T Download brochure
Print this page Print this page

  • Lightweight - only 13 kg
  • Test current 5 mA - 60 A DC
  • Measuring range 0,1 µΩ – 2 kΩ
  • Two voltage sense channels
  • Extremely quick measurement
  • Automatic discharge circuit
  • Built-in Tap Changer Control Unit
High DC current resistance meter for transformers & tap changer analyzer
Description

The Winding Ohmmeter & Tap Changer Analyzer RMO60T is designed for resistance measurement of inductive test objects. RMO60T generates true DC ripple free current. Both injection of current and discharge of energy from the inductance are automatically regulated.
RMO60T injects current with a voltage as high as 60 V. This ensures that the duration of test is as short as possible, and that the desired test current is reached faster. Two independent channels enable testing of two series windings, or primary and secondary windings. There is enough memory within RMO60T instrument to store 500 measurements. All measurements are time and date stamped.
The set is equipped with thermal and overcurrent protection. The RMO60T has very high ability to cancel electrostatic and electromagnetic interference in HV electric fields. It is achieved by very efficient filtration. The filtration is made utilizing proprietary hardware and software.

On Load Tap Changers

The RMO60T can be used to measure winding resistance of individual taps of a power transformer’s tap changer. It can also check whether the on-load tap changer (OLTC) switches without an interruption. The moment a tap position is changed from one tap to another, the device detects a sudden, very short drop of the current. A properly working tap changer differs from a malfunctioning one. This is obvious from an interruption during the change, by the magnitude of the current ripple and also by the transition time. Malfunctioning behaviour of Tap Changer will result in much higher current ripple value and by changed transition time than a properly functioning Tap Changer.
The Tap Changer Control Unit allows the operator to control the Tap Changer operation box from the RMO60T position.

DV-Win

Using DV-Win software, tests could be performed from a PC, and results can be obtained directly at a PC. The DV-Win software allows results to be arranged in an Excel spreadsheet, which can be shown later as a diagram and printed for a report, or ASCII format. This software can control the RMO-T instrument, allowing a condition assessment of OLTC (tap changer) analyzing the graph which represents dynamic resistance during the tap change. Using DV-Win and RMO60T it is possible to perform heat run test on distribution and power transformers.

Typical Application
Typical application of RMO60T is measuring the resistance of:
  • Power transformers
  • On-Load Tap Changers
  • Generators and electrical motors
  • High-current busbar joints
  • Cable splices
Standard accessories
  • DV-Win PC software
  • Current cables 2 x 10 m 10 mm2 and Sense cables 2 x 10 m 2,5 mm2
  • Sense cables 2 x 10 m 2,5 mm2
  • Current connection cable 1 x 5 m 10 mm2
  • Built-in Tap Changer Control Unit
  • Tap Changer Control cable set 5 m
  • Mains power cable
  • Ground (PE) cable
  • Cable bag
Standard Cables special clamps Voltage sense pair
Standard test cables Transformer terminals adjusted clamps Voltage sense cables - pair
Optional accessories
  • Built-in thermal printer
  • Test shunt 75 A / 150 mV
  • Current cables 2 x 15 m 10 mm2 and Sense cables 2 x 15 m 2,5 mm2
  • Sense cables 2 x 15 m 2,5 mm2
  • Cable plastic case
 
RMO60T Shunt cable bag
RMO60T Shunt Cable bag
 
Connecting a Test Object to RMO60T  

The RMO60T should be turned off, connection between RMO60T and the test object is such  that the measuring cables from the "Voltage Sense" sockets are attached as close as possible to the measured resistance, while they are connected between the current feeding cables. That way, resistance of cables and clamps is almost completely excluded from the resistance measured. The figure to the right shows simultaneous testing of both windings (high and low) on a single-phase transformer. In such a way, it is possible to speed up the measurement when two channels are used to test both windings of the transformer.

Testing of a Delta-delta winding resistance is usually a very time consuming procedure. This is because the two windings represent two closed loop inductors. When energy is brought into the inductors, this energy (in the form of D.C. current) continually circulates within each winding. To test this configuration quickly, both high and low sides should be connected in series with the current source of a Transformer Ohmmeter. By having these two windings in opposing polarity, the internal circulating currents settle very quickly to obtain a balance, and discharge with the same speed. Even if only one side of the transformer needs to be tested, connecting both high and low windings in series will speed up the test considerably.

Using RMO60T’s TapChanger menu, the power transformer winding resistance of individual tap positions can be measured. Also, you can check whether the on-load tap changer switches without an interruption.  The RMO60T current output injects a constant current into a power transformer. This current and voltage value is measured, and the winding resistance is calculated.
   
Technical data
1 Mains Power Supply  
- Connection according to IEC/EN60320-1; UL498, CSA 22.2
- Voltage single phase 110 - 240 V AC, +10 % - –15 %
- Frequency 50 / 60 Hz
2 Output data  
- Test current 5 mA DC- 60 A DC
- Measuring range Resolution
   0,1 µΩ - 999,9 µΩ 0,1 µΩ
   1,000 mΩ - 9,999 mΩ 1 µΩ
   10,00 mΩ - 99,99 mΩ 10 µΩ
   100,0 mΩ - 999,9 mΩ 0,1 mΩ
   1,000 Ω - 99,99 Ω 10 mΩ
   100,0 Ω - 999,9 Ω 0,1 Ω
   1000 Ω - 2000 Ω 1 Ω
- Typical accuracy ±(0,2 % rdg + 0,2 % FS)
3 Environment conditions
- Operating temperature -10 °C - +50 °C / 14 °F - +122 °F
- Storage and transportation -40 °C - +70 °C / -40 °F - +158 °F
- Humidity 5 % - 95 % relative humidity, non condensing
4 Dimensions and Weight
- Dimensions 502 mm x 190 mm x 395 mm
19,75 in x 7,48 in x 15,53 in
(W x H x D) without handle
- Weight 13 kg / 28,6 lb
5 Warranty three years
6 Safety Standards
- European standards EN 61010-1
LVD 73/23/EEC
- International standards IEC 61010-1
UL 3111-1
CAN/CSA-C22.2 No 1010.1-92
7 Electromagnetic Compatibility (EMC)
- CE conformity EMC standard 89/336/EEC
- Emission EN 50081-2, EN 61000-3-2/3
- Interference Immunity EN 50082-2

All specifications herein are valid at ambient temperature of + 25 °C and standard accessories. Specifications are subject to change without notice.