Winding Ohmmeter
RMO50M

RMO100M

Brochure RMO50M Download brochure
Print this page Print this page

  • Lightweight - only 8 kg
  • Test current 5 mA - 50 A DC
  • Measuring range 0,1 µΩ – 1 kΩ
  • Mechanical protection IP43
  • Extremely quick measurement
  • Automatic discharge circuit
High DC current resistance meter for motors/generators
Description

The Winding Ohmmeter RMO50M is designed for winding resistance measurement of electrical motors and generators. RMO50M generates true DC ripple free current. The test result is displayed as R=U/I.
The RMO50M instrument can store up to 500 measurements. All measurements are time and date stamped. Using RMOWin-M software a test can be performed from a PC, and the results can be obtained directly at a PC. Using RMOWin-M the result can be arranged as an Excel spreadsheet which can be later shown as a diagram and printed for a report. The RMO50M has very high ability to cancel electrostatic and electromagnetic interference in HV electric fields. It is achieved by very efficient filtration. The filtration is made utilizing proprietary hardware and software.

Typical Application
Typical application of RMO50M is measuring the resistance of:
  • Generators and electrical motors
  • High-current busbar joints
  • Cable splices
Standard accessories
  • RMOWin-M PC software
  • Mains power cable
  • Ground (PE) cable
Voltage sense cables Current cables
Voltage sense cables Current cables
Optional accessories
  • Current cables 2 x 5 m 10 mm2
  • Sense cables 2 x 5 m 2,5 mm2
  • Built-in thermal printer
  • Test shunt 150 A / 150 mV
  • Current cables 2 x 10 m 10 mm2
  • Sense cables 2 x 10 m 2,5 mm2
  • Transport bags
  • Transport case
 
Transport bags Shunt Transport case
Transport bags Shunt Transport case
 
Technical data
1 Mains Power Supply  
- Connection according to IEC/EN60320-1; UL498, CSA 22.2
- Voltage single phase 110 V - 240 V AC, +10 % - –15 %
- Frequency 50/60 Hz
2 Output data  
- Test current 5 mA DC- 50 A DC
- Measuring range Resolution
   0,1 µΩ - 999,9 µΩ 0,1 µΩ
   1,000 mΩ - 9,999 mΩ 1 µΩ
   10,00 mΩ - 99,99 mΩ 10 µΩ
   100,0 mΩ - 999,9 mΩ 0,1 mΩ
   1,000 Ω - 99,99 Ω 10 mΩ
   100,0 Ω - 1000 Ω 0,1 Ω
- Typical accuracy ±(0,2% rdg + 0,2% FS)
3 Environment conditions
- Operating temperature -10 °C - +50 °C / 14 °F - +122 °F
- Storage and transportation -40 °C - +70 °C / -40 °F - +158 °F
- Humidity 5 % - 95 % relative humidity, non condensing
4 Dimensions and Weight
- Dimensions 198 mm x 255 mm x 380 mm
7,8 in x 10 in x 15 in
(W x H x D) without handle
- Weight 8 kg / 17,6 lb
5 Mechanical protection IP43
6 Warranty three years
7 Safety Standards
- European standards LVD 2006/95/EC (EN 61010-1)
- International standards IEC 61010-1
UL 3111-1
CAN/CSA-C22.2 No 1010.1-92
8 Electromagnetic Compatibility (EMC)
- CE conformity EMC standard 2004/108/EC