Winding OhmMeter RMO100M

RMO100M

Brochure RMO100M Download brochure
Print this page Print this page

  • Lightweight - only 8 kg
  • Test current 10 mA - 100 A DC
  • Measuring range 0,1 µΩ –600 Ω
  • Mechanical protection IP54
  • Extremely quick measurement
High DC current resistance meter for motors/generators
Description

The ohmmeter RMO100M is designed for resistance measurement of electrical motors and generators. RMO100M generates true, filtered DC current. The test result is displayed as R=U/I. The RMO100M instrument can store up to 500 measurements. All measurements are time and date stamped. Using RMOWin-M software a test can be performed from a PC, and the results can be obtained directly at a PC. Using RMOWin-M the result can be arranged as an Excel spreadsheet which can be later shown as a diagram and printed for a report. The RMO100M has very high ability to cancel electrostatic and electromagnetic interference in HV electric fields. It is achieved by very efficient filtration. The filtration is made utilizing proprietary hardware and software.

Typical Application
Typical application of RMO100M is measuring the resistance of:
  • Generators and electrical motors
  • High-current busbar joints
  • Cable splices
Standard accessories
  • RMOWin-M PC software
  • Current cables 2 x 5 m 16 mm2 with battery clips
  • Sense cables 2 x 5 m 2,5 mm2 with alligator clips
  • Mains power cable
  • Ground (PE) cable
  • Transport case
Voltage sense cables Current cables
Voltage sense cables Current cables
Optional accessories
  • Built-in thermal printer
  • Test shunt 100A/100mV
  • Current cables 2 x 10 m 16 mm2 with battery clips
  • Sense cables 2 x 10 m 2,5 mm2 with alligator clips
  • Cable bag
 
Transport bags Shunt Transport case
Transport case Shunt Cable bag
 
Technical data
1 Mains Power Supply  
- Connection according to IEC/EN60320-1; UL498, CSA 22.2
- Voltage single phase 110 V- 240 V AC, +10% - –15%
- Frequency 50/60 Hz
2 Output data  
- Test current 10 mA DC- 100 A DC
- Measuring range Resolution
   0,1 µΩ - 999,9 µΩ 0,1 µΩ
   1,000 mΩ - 9,999 mΩ 1 µΩ
   10,00 mΩ - 99,99 mΩ 10 µΩ
   100,0 mΩ - 999,9 mΩ 0,1 mΩ
   1,000 Ω - 99,99 Ω 10 mΩ
   100,0 Ω - 600 Ω 0,1 Ω
- Typical accuracy ±(0,2% rdg + 0,2% FS)
3 Environment conditions
- Operating temperature -10°C - +50°C / 14°F - +122°F
- Storage and transportation -25°C - +70°C / -13°F - +158°F
- Humidity 5% - 95% relative humidity, non condensing
4 Dimensions and Weight
- Dimensions 198 mm x 255 mm x 380 mm
7,8 in x 10 in x 15 in
(W x H x D) without handle
- Weight 8 kg/17,6 lb
5 Safety Standards
- European standards EN 61010-1
- International standards IEC 61010-1
6 Electromagnetic Compatibility (EMC)
- CE conformity EMC standard 89/336/EEC
- Emission EN 50081-2, EN 61000-3-2/3
- Interference Immunity EN 50082-2