Micro Ohmmeter RMO100G

RMO200G

Brochure RMO100G Download brochure
Print this page Print this page

  • Lightweight - only 8 kg
  • Powerful   5 A - 100 A DC
  • Measuring range 0 – 999,9 mΩ
  • Resolution to 0,1 µΩ
  • SINGLE / CONTIN Mode
  • True DC current
High DC current resistance meter
Description

RMO100G is a Micro Ohmmeter based on state of the art technology, using the most advanced switch mode technique available today. RMO100G generates true DC current with automatically regulated test ramps. During the test RMO100G ramps with increasing current before measuring and decreasing current after the measurement. This eliminates magnetic transients. After the test current has been set, the automatic test procedure is started by pressing the START-button.
The RMO100G instrument can store up to 500 measurements. All measurements are time and date stamped. Using DV-Win software a test can be performed from a PC, and the results can be obtained directly at a PC. Using DV-Win the result can be arranged as an Excel spreadsheet which can be later shown as a diagram and printed for a report.
The set is equipped with thermal and overcurrent protection. The RMO100G has very high ability to cancel electrostatic and electromagnetic interference in HV electric fields. It is achieved by very efficient filtration. The filtration is made utilizing proprietary hardware and software.

Output Ratings
The full output is available from the RMO100G at 230 V Mains Supply. A reduced output is available from lower supply voltages.
Supply Voltage Output Current Full Load Voltage
230 V AC 100 A DC smoothed 6,0 V DC
115 V AC 100 A DC smoothed 6,0 V DC

Output current is filtered and has a ripple of less than 1 %. The RMO100G current output is rated at 100 A for 5 minutes at 25 °C ambient temperature.

CONTIN Mode
RMO100G can generate DC current continuously using the CONTIN menu. In this menu the current can be chosen the same way like in the SINGLE menu, but the duration of the test can be preset. The test is started pressing the START-button. During the test, a new result is shown on the display and stored into the PC (DV-Win) each second. Using DV-Win the result can be arranged as an Excel spreadsheet which can be later shown as a diagram and printed for a report.
Application
Typical application is measuring resistance of:
  • High, middle and low voltage circuit breakers
  • High, middle and low voltage disconnecting switches
  • High-current bus bar joints
  • Cable splices
  • Welding joints
Accessories
Included
  • DV-Win PC software
  • Mains power cable
  • Ground (PE) cable
Recommended
  • Current cables 2 x 5 m 16 mm2 with battery clips
  • Sense cables 2 x 5 m with alligator clips
  • Cable bag
Voltage sense cables Current cables Extension cable
Voltage sense cables Current cables Extension cable
Optional
  • Built-in thermal printer
  • Remote control unit
  • Both sides grounded unit
  • Test shunt 100 µΩ
  • Current cables 2 x 10 m 16 mm2 with battery clips
  • Current cables 2 x 15 m 25 mm2 with battery clips
  • Extension cable 2 x 10 m 25 mm2
  • Sense cables 2 x 10 m with alligator clips
  • Sense cables 2 x 15 m with alligator clips
  • Cable plastic case
 
RMO200G Shunt Cable bag
RMO100G Shunt Cable bag
 
Connecting a Test Object to RMO100G
With RMO100G turned off, connect RMO100G to the test object (RX) in such a way that the measuring cables from the "Voltage Sense" sockets are attached as close as possible to RX, and in between the current feeding cables. That way, resistance of both cables and clamps is almost completely excluded from the resistance measurement.
Remote Control Unit
The RMO Remote Control Unit is an optional control unit that is used to start and stop the tests from a remote location, away from the actual RMO. Provided that, for a series of tests, the same test current is fed through the test object, multiple measurements can be carried out with the RMO Remote Control Unit.
   
Both Sides Grounded Unit
Using RMO100G with current clamp meter it is possible to make safer measurement of breakers with both terminals of the breaker grounded. It is performed by measuring the current through the ground connection and reducing this value from the total current.
   
Technical data
1 Mains Power Supply  
- Voltage 110 – 230 V AC
- Frequency 50 – 60 Hz
- Input power 1160 VA
- Fuse 12 A / 230 V, type F
2 Output data  
- Test current 5 A - 100 A DC
- Measuring range Resolution
   0,1 µΩ - 999,9 µΩ 0,1 µΩ
   1,000 mΩ - 9,999 mΩ 1 µΩ
   10,00 mΩ - 99,99 mΩ 10 µΩ
   100,0 mΩ - 999,9 mΩ 0,1 mΩ
- Typical accuracy ± (0,2 % rdg + 0,2 % FS)
3 Environment conditions
- Operating temperature -10 °C - +55 °C / 14 F - 131 F
- Storage temperature -40°C - +70 °C / 40 F - 158 F
- Maximum relative humidity 95 % non-condensing

- Mains supply voltage fluctuations up to ±10 % of the nominal voltage

- Installation/overvoltage category II

- Pollution degree 2

4 Dimensions and Weight
- Dimensions 410 mm x 180 mm x 320 mm
16,14 in x 7,08 in x 12,59 in
(W x H x D) without handle
- Weight 8 kg/17,5 lb
5 Warranty three years
6 Safety Standards
- European standards EN 61010-1
LVD 2006/95/EC
- International standards IEC 61010-1
UL 61010-1
CAN/CSA-C22.2 No. 61010-1, 2nd edition, including Amendment 1
7 Electromagnetic Compatibility (EMC)
- CE conformity EMC standard 89/336/EEC
EMC directive 2004/108/EC
- Emission EN 61326-1
- Interference Immunity EN 61326-1