| Coil Tester & Breaker Supply POB30AD |

Brochure POB30AD 
Print this page  |
- Lightweight - only 9 kg
- Powerful - up to 30 A
- Voltage 10 V to 300 V DC
- Voltage 10 V to 250 V AC
- Output protection
- Fully automatic operation
|
| Powerful DC and AC power supply for a circuit breaker test |
| Description |
POB30AD is a power supply unit employing the latest power electronics technology. POB30AD generates ripple free DC-voltage and it is developed for regular maintenance tests of power circuit breakers. POB30AD generates also AC voltage. Output voltage is selectable from 10 V to 300 V DC or from 10 V to 250 V AC.
The POB30AD is powerful and versatile unit, with possibility to generate at 230 V mains supply initial current up to 30 A as well as continuous current according to the tables below: |
| 230 V |
110 V DC |
24 A
20 A
10 A |
20 sec
60 sec
30 min |
| 220 V DC |
12 A
10 A
7 A |
20 sec
60 sec
30 min |
| 115 V |
110 V DC |
12 A
10 A
7 A |
20 sec
60 sec
30 min |
| 220 V DC |
7 A
6 A
5 A |
20 sec
60 sec
30 min |
|
| 230 V |
110 V AC |
10 A
5 A |
800 msec
30 min |
| 220 V AC |
10 A
5 A |
800 msec
30 min |
| 115 V |
110 V AC |
10 A
5 A |
800 msec
30 min |
| 220 V AC |
10 A
5 A |
800 msec
30 min |
|
The set is equipped with thermal and overcurrent protection. POB30AD is easy to use and has accessory cable-set with touch-proof contacts.
The POB30AD has very high ability to cancel electrostatic and electromagnetic interference in HV electric fields. It is achieved by very efficient filtration. The filtration is made utilizing proprietary hardware and software. |
| Applications |
| POB30AD is developed for use in switchyards, electric power and industrial environment. An important part of commissioning and maintenance testing is a circuit breaker testing.
POB30AD is possible to use for: |
- operating circuit breakers
- supplying spring-charging motors
- power supply at test with breaker analysers
- minimum trip-voltage test of the circuit breaker's coils
|
| POB30AD have built-in capability to perform an automatic test of minimum trip-voltage. The minimum trip- voltage test is described in a number of international and national standards such as IEC 62271-100, ANSI C37.09 etc. Many other important parameters are possible to test with a breaker analyser. POB30AD is then used as a power supply unit. It is compatible with breaker analysers from different vendors. POB30AD can also be used as a general power supply unit or a temporary battery charger. |
| Automatic testing of the minimum trip voltage of a breaker |
Procedure steps:
1. Make certain that the mains are de-energised on both sides of the breaker, safety
grounded and that local safety regulations are followed.
2. Connect Power supply unit POB30AD to the breaker's coil circuit.
3. Set the minimal test voltage.
4. Set the step voltage.
5. Set the maximal voltage.
6. Press TRIG button. |
| Standard accessories |
- Cable set 6 x 2 m 2,5 mm2
- Extern trigger cable set 2 m
- Mains power cable
- Ground (PE) cable
- Transport bags
|
| Optional accessories |
- Cable plastic case
- Transport case
|
| |
 |
|
 |
| Transport case |
|
Cable set |
|
| |
| Technical data |
| 1 Mains Power Supply |
| - Connection |
according to IEC/EN60320-1; UL498, CSA 22.2 |
| - Voltage single phase |
110 V - 240V AC, +10% - –15% |
| - Frequency |
50/60Hz |
| 2 Output data |
| - Coils output DC Voltage |
10 V to 300 V DC |
| - Coils output AC Voltage |
10 V to 250 V AC; 50/60Hz; true RMS |
| - Motor output DC Voltage |
10 V to 250 V DC |
| - Output Current |
max 30 A |
| 3 Measurement |
| - Voltage |
10 V - 300 V DC or 10 V - 250 V AC |
| - Current |
1 A - 50 A |
| - Accuracy |
±(0,5% rdg + 0,5% FS) |
| 4 Environment conditions |
| - Operating temperature |
-10°C - +50°C / 14°F - +122°F |
| - Storage and transportation |
-40°C - +70°C / -40°F - +158°F |
| - Humidity |
5% - 95% relative humidity, non condensing |
| 5 Dimensions and Weight |
| - Dimensions |
198 mm x 255 mm x 380 mm
7,8 in x 10 in x 15 in
(W x H x D) without handle |
| - Weight |
9 kg/19,8 lb |
| 6 Mechanical protection |
IP43 |
| 7 Safety Standards |
| - European standards |
LVD 2006/95/EC (EN 61010-1) |
| - International standards |
IEC 61010-1
UL 3111-1
CAN/CSA-C22.2 No 1010.1-92 |
| 8 Electromagnetic Compatibility (EMC) |
| - CE conformity |
EMC standard 2004/108/EC |
|
| |