Three-Phase
Transformer
Demagnetizer DEM60 |

Brochure DEM60 
Print this page 
|
| |
- Fully automatic demagnetization
- Demagnetization currents 5 mA – 60 A DC
- Automatic discharging circuit
- Lightweight – 10,5 kg
|
| High DC Current Source for Automatic Demagnetization Transformers and CTs |
| Description |
After a DC current test, such as a winding resistance measurement, the magnetic core of a power or instrument transformer may be magnetized (remanent magnetism). Also, when disconnecting a transformer from service, some amount of magnetic flux trapped in the core could be present.
The remanent magnetism can cause various problems such as erroneous diagnostic electrical measurements on a transformer, or an inrush current at start-up of power transformer, or incorrect operation of protective relays due to magnetized CT cores.
To eliminate this source of potential problems, demagnetization should be performed.
When suspecting remanent magnetism, or when various test results, like FRA or magnetization/excitation current, show possible remanency use the DEM60 to perform fully automatic demagnetization.
Demagnetizing magnetic core of a transformer requires alternating current applied with decreasing magnitude down to zero. The DEM60 provides this alternating current by internally changing the polarity of a controlled DC current. During the demagnetization process the instrument supplies current at decreasing magnitude for each step, following a proprietary developed program.
|
| |
 |
| DV-Win |
Using DV-Win software, instrument can be operated and controlled from a PC. The standard interface is USB and optional RS232. |
| Discharging Circuit |
Both injection of current and discharging energy from the inductance is automatically regulated. An intrinsically safe discharge circuit with indicator dissipates the stored magnetic energy rapidly during and after the operation. The discharging circuit is independent of power supply. |
| Accessories |
| Included |
 |
| Current cables |
|
- DV-Win PC software
- Mains power cable
- Ground (PE) cable
|
| Recommended |
- Current cables 4 x 10 m 10 mm2 with clamps
- Cable plastic case
|
| Optional |
- Current cables 4 x 15 m 10 mm2
- Cable bag
|
|
| |
|
| Technical data |
| 1 Mains Power Supply |
|
| - Voltage |
110 – 230 V AC |
| - Frequency |
50 – 60 Hz |
| - Input power |
2250 VA |
| - Fuse |
15 A / 250 V, type F |
| 2 Output data |
|
| - Test current |
5 mA DC - 60 A DC |
| - Test voltage |
60 V DC |
| 3 Environment conditions |
| - Operating temperature -10 °C - +55 °C / 14 F - 131 F |
| - Storage temperature -40°C - +70 °C / 40 F - 158 F |
| - Maximum relative humidity 95 % non-condensing |
| - Mains supply voltage fluctuations up to ±10 % of the nominal voltage |
| - Installation/overvoltage category II |
| - Pollution degree 2 |
| 4 Dimensions and Weight |
| - Dimensions |
450 x 175 x 320 mm (W x H x D)
17,72 x 6,89 x 12,6 in |
| - Weight |
10,5 kg / 23,1 lb |
| 5 Warranty |
three years |
| 6 Safety Standards |
| - European standards |
LVD 2006/95/EC
EN 61010-1 |
| - International standards |
IEC 61010-1
UL 61010-1
CAN/CSA-C22.2 No. 61010-1, 2nd edition, including Amendment 1 |
| 7 Electromagnetic Compatibility (EMC) |
| - CE conformity |
EMC directive 2004/108/EC |
| - Emission |
EN 61326-1 |
| - Immunity |
EN 61326-1 |
Specifications are subject to change without notice. |
|
|