Circuit Breaker Analyzers and Timers Print this page Print this page
Circuit Breaker Analyzer and Timer CAT series instruments are designed for condition assessment of circuit breakers. Timing channels record closing and opening of main contacts, resistor contacts, and auxiliary contacts. CAT instruments records graphs of both Open and Close coil currents and displacements of HV and MV circuit breaker moving parts. Main contact channels can also measure resistance value of pre-insertion resistors (if present in the circuit breaker).
Test results are printed on an 80 mm thermal printer in tabulated and graphical form. User can select any desired operational mode: Close (C), Open (O), Close-Open (C-O), Open-Close (O-C), Open-Close-Open (O-C-O).
CAT instruments are supplied with DV-Win software, which provides full control of all CAT functions from a PC, acquisition and analysis of test results.
Typical application areas of CAT instruments are high-voltage substations and industrial environments. An important part of commissioning, maintaining and production of circuit breakers are:
  • Simultaneous measurement of Main contacts and auxiliary contacts, including pre-insertion resistors
  • Resistance measurement of pre-insertion resistors
  • Evaluation of the synchronization between the circuit breaker poles
  • Measurement of coil currents, simultaneously for both coils
  • Evaluating the state of the substation’s batteries by graphically showing the voltage value
  • Measurement of stroke, contact wipe, over-travel, rebound and average velocity of breaker’s moving parts
  • "First trip” test available

Circuit Breaker Analyzers and Timers CAT30 series
  CAT03 CAT30 CAT31 CAT32 CAT33 CAT34
TIME MEASURING CHANNELS 3 3 3 3 3 3
COIL OPERATION NO YES YES YES YES YES
COIL CURRENT MEASUREMENT NO YES YES YES YES YES
TRIGGER INPUT YES YES YES YES YES YES
AUX CONTACTS TIMING CHANNELS NO 1 3 3 3 3
ANALOG INPUTS NO NO NO YES YES YES
ANALOG TRANSDUCER INPUT NO NO NO YES NO YES
DIGITAL TRANSDUCER INPUT NO NO NO NO YES YES
FIRST TRIP TEST NO NO NO YES YES YES
PC SOFTWARE YES YES YES YES YES YES
BUILT-IN THERMAL PRINTER OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL
 
Circuit Breaker Analyzers and Timers CAT60 series
  CAT60 CAT61 CAT62 CAT63 CAT64
TIME MEASURING CHANNELS 6 6 6 6 6
COIL OPERATION YES YES YES YES YES
COIL CURRENT MEASUREMENT YES YES YES YES YES
TRIGGER INPUT YES YES YES YES YES
AUX CONTACTS TIMING CHANNELS 1 3 3 3 3
ANALOG INPUTS NO NO YES YES YES
ANALOG TRANSDUCER INPUT NO NO YES NO YES
DIGITAL TRANSDUCER INPUT NO NO NO YES YES
FIRST TRIP TEST NO NO YES YES YES
PC SOFTWARE YES YES YES YES YES
BUILT-IN THERMAL PRINTER OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL
 
Accessories
Cables

DV Power provides Main contacts cable set for time measurement, with different alligator clips. Coil control cable set, Auxiliary cable set and External Trigger cable set can have different terminations:

 
Terminations available for Coil control cable,
Auxiliary cable and External trigger cable
Digital rotary transducer
Allows for very accurate motion measurement. Digital transducers don’t need to be re-calibrated.
Mounting becomes easier due to the fact that this transducer has no zero point.

Linear analog transducers
Linear analog transducers allow for motion measurement of circuit breaker's moving parts.
Linear transducers are available in several lengths. Please contact DV Power for more information.
Built-in thermal printer
We deliver CAT series devices with 80 mm paper wide built-in thermal printer, as an optional accessory.
Current clamps
Current clamps can be connected to Low voltage analog input in order to capture the “first trip” test and evaluate the condition of the circuit breaker mechanism that has been stationary for a long time.

Transducer mounting kit
The kit is very flexible and can be mounted in a number of different positions, both on the circuit breakers poles and operating mechanisms.
  • Big clamping base
  • Small clamping base
  • Articulated arm
  • Magnetic base